GDTF-108/108 | |
Input voltage (V) | 380 |
Output voltage (kV) | 0-108 |
Capacity (kVA) | 108 |
Application scope | 31500kVA or below |
35kV power transformer | |
35kV circuit breaker and bus bar, insulators | |
10kV (300 mm²) cable 2000m | |
35k V (300 mm²)cable 500m | |
Main configurations | 5kW Variable frequency source 1 set |
5kVA Exciting transformer 1 set | |
Reactors 27kV/1A 4sets | |
Capacitive divider 100kV | |
GDTF-216/216 | |
Input voltage (V) | 380 |
Output voltage (kV) | 0-216 |
Capacity (kVA) | 216 |
Application scope | 110kV Circuit breaker and bus bar |
110kV GIS | |
35kV(300 mm²) cable 1500m | |
10kV(300 mm²) cable 3km | |
110kV full insulation Transformer | |
Main configurations | 10kW Variable frequency source 1 set |
10kVA Exciting transformer 1 set | |
Reactors 54kV/1A 4sets | |
Capacitive divider 200kV | |
GDTF-270/270 | |
Input voltage (V) | 380 |
Output voltage (kV) | 0-270 |
Capacity (kVA) | 270 |
Application scope | 110kV GIS and transformer |
110kV GIS and transformer | |
35kV (300 mm²) cable 2km | |
Main configurations | 15kW Variable frequency source 1 set |
15kVA Exciting transformer 1 set | |
Reactors 54kV/1A 5sets | |
Capacitive divider 300kV | |
GDTF-400/400 | |
Input voltage (V) | 380 |
Output voltage (kV) | 0-400 |
Capacity (kVA) | 400 |
Application scope | 220kV GIS and transformer |
10kV (300 mm²) cable 4km | |
35kV (300 mm²) cable 1km | |
Main configurations | 20kW Variable frequency source 1 set |
20kVA Exciting transformer 1 set | |
Reactor | |
Capacitive divider 400kV | |
GDTF-520/260 | |
Input voltage (V) | 380 |
Output voltage (kV) | 0-260 |
Capacity (kVA) | 520 |
Application scope | 110KV Circuit breaker and bus bar |
110kV GIS | |
110kV (300 mm²) cable 800m | |
35kv (300 mm²) cable 3km | |
10kV (300 mm²) cable 6km | |
110kv full insulation Transformer | |
Main configurations | 25kW Variable frequency source 1 set |
25kVA Exciting transformer 1 set | |
Reactor 65kV/2A 4sets | |
Capacitive divider 300kV | |
GDTF-500/500 | |
Input voltage (V) | 380 |
Output voltage (kV) | 0-500 |
Capacity (kVA) | 500 |
Application scope | 220kV or below CT/PT |
220kV or below bushing | |
220kV or below Insulators, disconnectors | |
220kV or below Circuit breaker | |
220kV or below Insulation Instrument | |
Main configurations | 20kW Variable frequency source 1 set |
20kVA Exciting transformer 1 set | |
Reactor 125kV/1A 4sets | |
Capacitive divider 500kV | |
GDTF-600/600 | |
Input voltage (V) | 380 |
Output voltage (kV) | 0-600 |
Capacity (kVA) | 600 |
Application scope | 110kV (300 mm²) cable 800m |
35kv (300 mm²) cable 110m | |
35-220kV GIS, transformers, insulators | |
Main configurations | 30kW Variable frequency source 1 set |
30kVA Exciting transformer 1 set | |
Reactor 120kV/1A 5sets | |
Capacitive divider 600kV | |
GDTF-800/800 | |
Input voltage (V) | 380 |
Output voltage (kV) | 0-800 |
Capacity (kVA) | 800 |
Application scope | 110kV (300 mm²) cable 800m |
220kv (300 mm²) cable 500m | |
35-500kV GIS, transformers, insulators | |
Main configurations | 40kW Variable frequency source 1 set |
40kVA Exciting transformer 1 set | |
Reactor 200kV/1A 4sets | |
Capacitive divider 800kV |
Specification
● Rated output voltage: based on different test objects.
● Output frequency: 20- 300Hz.
● Waveform: pure sine wave, THD <1.0%.
● Max. capacity: 1000kVA and below.
● Duty Cycle: Continuous working time 15mins one time at full power output. (or customer demand.)
● Frequency adjustment sensitivity: 0.1Hz, instability <0.05%.
● Power Supply: 380/220V ± 15%/50Hz ± 5%.