According to IEC and relevant national standards, the transformer ratio test is a must-do item during the production, user handover, and overhaul test of power transformers. This can effectively supervise the quality of the transformer products during delivery and use, and prevent short circuits, open circuit, wrong connection between transformer turns, and internal failure or contact failure of the regulator switch.

facebook sharing button
twitter sharing button
linkedin sharing button
pinterest sharing button
vk sharing button
whatsapp sharing button
sharethis sharing button
Chat Now
Product Introduction

GDB-II Transformer Turns Ratio Tester

 

●Easy and simple operation.

●Test single phase and three phase oil transformers.

●Measure transformer connection groups automatically.

 ●Fast measurement speed.

 ●After one measurement is completed, the test power supply is automatically

cut off.

●Save the test data automatically, and previous data can be viewed.

 ●When testing the on-load transformer, only input the transformation ratio

once.

●Easy to carry, suitable for field work.


Specification

 

●Measurement range of ratio: 1-9999.9

●Accuracy: 1-999.99  0.2%; 1000-9999.9  0.5%

●Power supply: 220V±10%, 50Hz

 Group: 1-12

●Working temperature: -10--40℃

●Environment humidity: <80% no-condensation