enLanguage
Home / MOA Tester/GDYZ-301A Zinc Oxide Surge Arrester Tester
GDYZ-301A Zinc Oxide Surge Arrester Tester

GDYZ-301A Zinc Oxide Surge Arrester Tester

GDYZ-301A Automatic Zinc Oxide Surge Arrester Tester contains below three functions:Resistive current testCurrent meter calibration of monitorCounter action test of monitor

facebook sharing button
twitter sharing button
linkedin sharing button
pinterest sharing button
vk sharing button
whatsapp sharing button
sharethis sharing button
Chat Now
Product Introduction

GDYZ-301A Zinc Oxide Surge Arrester Tester

 

It is the special equipment of testing zinc oxide electric performance. The instrument can accurately and stably measure the arrester resistive current and the monitor counter action parameters while the equipment is running. It can also check the monitor ammeter. 

 8inch color LCD touch screen, high speed thermal printer.
 The measurement data of wire and wireless is the same.
 Wireless sampling, with long distance.
A. Wired: indoor use, or on-site where the PT sampling wiring cabinet is near with tested lightning arrester.
B. Wireless: outdoor use, or on-site where the PT sampling wiring cabinet is far from tested lightning arrester, wireless distance is up to 1000M.
 Three-phase can be measured at the same time. The resistive current of 3channels can be measured at the same time, meanwhile, there are two anti-interference modes: 1) no interference: the interphase angle cannot be calculated and corrected automatically under this mode; 2) With interference: the interphase interference angle can be calculated and corrected. Only one time connection to finish measurement of ABC phase.
 Built-in high capacity Li-battery, suitable for no power supply field.

Specification

 

Use condition-20℃- 50℃RH<80%
Charging power supplyAC 220V±10%
Input range of PT reference voltage0-300V
Input resistance of voltage channel150kΩ(with fuse)
Measuring accuracy of PT reference voltage±(2% of the reading+0.5V)
Measuring range of current input0-10mA
Measurement accuracy of current fundamental±(2% of the reading+5μA)
Measurement accuracy of current harmonic±(5% of the reading+10μA)
Input resistance of current channel≤1Ω
Action times of monitor0~99times
8/20μS impulse current≥50Ap
Calibration range of current meter0-10mA
Calibration accuracy of current meter±(2% of the reading+5μA)
Measurement resolutionVoltage0.001V
Current0.001mA
Angle0.001°
Battery working timeMain unit 8hours, voltage sampling box 12hours
Wireless transmission distance1000meters and above(empty and unobstructed)
Dimension of main unit320×270×140mm
Handheld collection probe180×120×80mm
Weight of main unit4kg(without accessories)


Send Inquiry