GDPDS-341 SF6 Electrical Insulation State Comprehensive Analyzer

GDPDS-341 SF6 Electrical Insulation State Comprehensive Analyzer

At present, the UHV voltage level of 110KV and above uses SF6 gas-insulated enclosed GIS as the main primary equipment of the substation, the evaluation of GIS internal insulation status is mainly achieved by partial discharge detection method and SF6 gas chemical analysis method at home and abroad.

facebook sharing button
twitter sharing button
linkedin sharing button
pinterest sharing button
vk sharing button
whatsapp sharing button
sharethis sharing button
Chat Now
Product Introduction

GDPDS-341 SF6 Electrical Insulation State Comprehensive Analyzer

 

At present, the UHV voltage level of 110KV and above uses SF6 gas-insulated enclosed GIS as the main primary equipment of the substation, the evaluation of GIS internal insulation status is mainly achieved by partial discharge detection method and SF6 gas chemical analysis method at home and abroad. When partial discharge occurs in the early stage of insulation degradation inside the GIS, it will cause serious safety hazards to its safe operation. The detection methods of partial discharge mainly include three methods: ultra-high frequency partial discharge test, ultrasonic partial discharge test, and chemical detection of SF6 gas composition. At present, there are separate devices for these types of test methods on the market. For on-site GIS partial discharge live detection, two professional technicians in electrical and chemistry are required to carry multiple equipments at the same time to carry out partial discharge and SF6 gas detection, both flexibility and timeliness are too poor. In view of the current situation of partial discharge detection in GIS, HV HIPOT company introduced the international advanced technology to develop SF6 electrical insulation state comprehensive analyzer. The combination of UHF method, ultrasonic method and SF6 gas analysis in one equipment can improve the detection efficiency and judgment method of partial discharge defects in GIS equipment, and improve the accuracy of partial discharge judgment, provide reliable technical support for maintenance decision.

In addition to the SF6 gas analysis part, the SF6 electrical insulation state comprehensive analyzer also integrates partial discharge detection technology. Operators can use the partial discharge detection equipment to conduct preliminary partial discharge test and inspection on the tested electrical equipment. Once the electrical equipment is found to be suspected of partial discharge insulation failure, the SF6 gas analysis part can be used immediately to conduct SF6 gas sampling, physical and chemical analysis. The insulation condition of the tested object can be determined by querying the corresponding national standards through the physical and chemical analysis results. At the same time, SF6 gas analysis and partial discharge test can be carried out simultaneously. By synthesizing the data of physical quantity and chemical quantity, we can more accurately judge the insulation condition and fault cause of electrical equipment.

The main advantage of the SF6 electrical insulation status comprehensive analyzer is that it can comprehensively determine the insulation status of electrical equipment through the two results of partial discharge and SF6 gas physical and chemical analysis, and can determine the operating status of electrical equipment more quickly and accurately. It can also be used as a portable comprehensive testing equipment for on-site testing of SF6 gas micro-water, purity, and decomposition products.


 Partial discharge and analysis of trace moisture, purity and decomposition products of SF6 gas electrical equipment for electric power.
 SF6 gas cylinder gas quality test.
 Quality test of SF6 gas for recovery and reuse.
 High purity gas manufacturing.
 Semiconductor industry dry gas supply.
 Research and development use.
 Clean room/dry house monitoring.
 Metal heat treatment site and laboratory industrial gas humidity detection, such as air, CO2, N2, H2, O2, SF6, He, Ar and other inert gases.

Specification

 

Partial discharge detection part:

PD signal acquisition host

CPU Working frequency

1.2GHz

Operating system

Linx embedded operating system

Wired network port

LAN network port

Wireless network port

Built-in wireless WiFi

System running memory

512M

System storage memory

256M

Data acquisition frequency

250MHz

Ultrasonic detection channel

Measurement range

AE: 0-10mV;

AA: 0-100dBuV

Frequency detection range

20~200kHz

UHF detection channel

Detection frequency

300~1800MHz

Measurement range

-80~0dBm

Error

±1dBm

Resolution

1dBm

HFCT detection channel

Frequency range

0.5~100MHz

Error

±1dB

Sensitivity

15mV/1mA

Dynamic Range

60dB

Measurement range

0-1000mV

Accuracy

1dB

TEV detection channel

Frequency range

3~100MHz

Measurement range

0-60dBmV

Sensitivity

0.01mV

Error

±1dBmV

Resolution

1dBmV

Battery

Built-in battery

Lithium battery, 12V, 6000mAh

Use time

about 10 hours

Charging time

About 4 hours

Battery protection

Over-voltage and over-current protection

Battery charger

Rated voltage

12.6V

Charging output current

2A

Operating temperature

-20℃-60℃

Operating humidity

<80%

Data display and analysis terminal

The software is suitable for any terminal host with Windows system, and users can choose it by themselves.

Working environment

Working temperature

-20℃~50℃

Environment humidity

0~90%RH

IP level

54

SF6 gas analysis part

SF6 Humidity
 Measurement method: Resistive and Capacitive measurement principle
 Measurement range: dew point -80℃--+20℃ (support ppmv)
 Accuracy: ±1℃
(when the dew point temperature is below 0 ℃, the sensor output is the frost point)
 Response time: 63% [90%]
+20→-20℃ Td 5s[45s]
-20→-60℃ Td 10s[240s]
 Resolution: 0.01℃
 Repeatability: ± 0.5 ℃
 Display unit: ℃, ppm, ℃P20(converted value at 20℃)

SF6 Purity
 Measurement method: Infrared Measurement Principle (NDIR series sensors)
 Measuring range: 0 ~ 100% SF6
 Response time: [90%] 60s
 Accuracy: ± 0.5%FS
 Repeatability: ± 0.5%
 Resolution: 0.01%
 Display unit: %

SF6 Decomposition Products
 Measurement method: Electrochemical Measurements Principle (Electrochemical series sensors)
 Measurement range: H2S: 0 ~ 100ppmv
SO2: 0 ~100ppmv
CO: 0 ~ 500ppmv
HF: 0 ~ 50ppmv
 Resolution: 0.5ppmv
 Display unit: ppmv

Gas Flow
 Dew point measurement: SF6 and other gas: 400-600ml/min
SF6 purity measurement: 300-450ml/min
SF6 Decomposition Products: 250-300ml/min
 Flow display: 0-1000mL digital flow meter
 Sample gas pressure: ≤1MPa
 Sensor protection: Stainless steel sintered filter
 Power supply: 110-220VAC±10%, 50Hz, AC/DC use, over-charge protection, continuous working is no lower than 8hours.
 Use environment temperature: -20--+60℃
 Operation environment: temperature: -35 - 70℃
   Pressure: 0 - 20bar
   Sample gas flow rate: no-effect
 Humidity: 90%RH
 Dimension: 570*418*320mm
 Weight: about 18kg.